Engcore Ltd — Expertise and reliability
ABB 2CDS273001R0634 S203MC63 MCB TP 10KA
ABB Ltd

ABB 2CDS273001R0634 S203MC63 MCB TP 10KA

Standards: IEC/EN 60898-1 IEC/EN 60947-2

Fiche technique

RéférenceS203MC63
MarqueABB Ltd
CatégorieDisjoncteurs (MCB)
RemarksIP40 in enclosure with cover
StandardsIEC/EN 60898-1 IEC/EN 60947-2
Power Loss14.4 W at Rated Operating Conditions per Pole 4.8 W
Actuator TypeInsulation group II, black, sealable
Terminal TypeScrew Terminals
Number of Poles3
Actuator MarkingI / O
Housing MaterialInsulation Group II, RAL 7035
Pollution Degree3
Actuator MaterialInsulation Group II, Black, Sealable
Installation Sizeacc. to DIN 43880 1
Mounting PositionAny
Tightening Torque2.8 N·m
Caractéristique 1Rated Ultimate Short-Circuit Breaking Capacity (I cu ): (230 V AC) 25 kA (440 V AC) 15 kA
Caractéristique 2Rated Service Short-Circuit Breaking Capacity (I cs ): (230 V AC) 18.8 kA
Caractéristique 3Resistance to Shock acc. to IEC 60068-2-27: 25g / 2 shocks / 13 ms
Caractéristique 4Resistance to Vibrations acc. to IEC 60068-2-6: 5g, 20 cycles at 5 … 150 … 5 Hz with load 0.8 In
Connecting CapacityBusbar 10 / 10 mm² Flexible with Ferrule 0.75 … 25 mm² Flexible 0.75 … 25 mm² Rigid 0.75 … 35 mm² Stranded 0.75 … 35 mm²
Operational VoltageMaximum (Incl. Tolerance) 440 V AC Maximum 440 V AC Minimum 12 V AC Minimum 12 V DC
Rated Frequency (f)50 Hz 60 Hz
Screw Terminal TypeFailsafe Bi-directional Cylinder-lift Terminal
Degree of ProtectionIP20
Electrical Endurance10000 AC cycle
Mounting on DIN RailTH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715 TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715
Overvoltage CategoryIII
Rated Current (I n )63 A
Energy Limiting Class3
Built-In Depth ( t 2 )69 mm
Ambient Air TemperatureOperation -25 … +55 °C Storage -40 … +70 °C
Dielectric Test Voltage50 / 60 Hz, 1 min: 2 kV
Power Supply ConnectionArbitrary
Tripping CharacteristicC
Environmental Conditions28 cycles with 55 °C / 90-96 % and 25 °C / 95-100 %
Recommended Screw DriverPozidriv 2
Number of Protected Poles3
Rated Operational Voltageacc. to IEC 60898-1 400 V AC acc. to IEC 60947-2 440 V AC
Contact Position IndicationRed ON / Green OFF
Mechanical Endurance (N endu )20000 cycle
Rated Insulation Voltage (U i )acc. to IEC/EN 60664-1 440 V
Reference Ambient Air Temperature30 °C
Rated Short-Circuit Capacity (I cn )(400 V AC) 10 kA
Rated Impulse Withstand Voltage (U imp )4 kV (6.2 kV @ sea level) (5.0 kV @ 2000 m)
Les tarifs sont réservés à nos clients. Connectez-vous ou demandez un devis pour obtenir un prix et passer commande.