ABB Ltd
ABB 2CDS273001R0164 S203MC16 MCB TP 10KA
Standards: IEC/EN 60898-1 IEC/EN 60947-2
Fiche technique
| Référence | S203MC16 |
|---|---|
| Marque | ABB Ltd |
| Catégorie | Disjoncteurs (MCB) |
| Remarks | IP40 in enclosure with cover |
| Standards | IEC/EN 60898-1 IEC/EN 60947-2 |
| Power Loss | 7.5 W at Rated Operating Conditions per Pole 2.5 W |
| Actuator Type | Insulation group II, black, sealable |
| Terminal Type | Screw Terminals |
| Number of Poles | 3 |
| Actuator Marking | I / O |
| Housing Material | Insulation Group II, RAL 7035 |
| Pollution Degree | 3 |
| Actuator Material | Insulation Group II, Black, Sealable |
| Installation Size | acc. to DIN 43880 1 |
| Mounting Position | Any |
| Tightening Torque | 2.8 N·m |
| Caractéristique 1 | Rated Ultimate Short-Circuit Breaking Capacity (I cu ): (230 V AC) 25 kA (440 V AC) 15 kA |
| Caractéristique 2 | Rated Service Short-Circuit Breaking Capacity (I cs ): (230 V AC) 18.8 kA |
| Caractéristique 3 | Resistance to Shock acc. to IEC 60068-2-27: 25g / 2 shocks / 13 ms |
| Caractéristique 4 | Resistance to Vibrations acc. to IEC 60068-2-6: 5g, 20 cycles at 5 … 150 … 5 Hz with load 0.8 In |
| Connecting Capacity | Busbar 10 / 10 mm² Flexible with Ferrule 0.75 … 25 mm² Flexible 0.75 … 25 mm² Rigid 0.75 … 35 mm² Stranded 0.75 … 35 mm² |
| Operational Voltage | Maximum (Incl. Tolerance) 440 V AC Maximum 440 V AC Minimum 12 V AC Minimum 12 V DC |
| Rated Frequency (f) | 50 Hz 60 Hz |
| Screw Terminal Type | Failsafe Bi-directional Cylinder-lift Terminal |
| Degree of Protection | IP20 |
| Electrical Endurance | 20000 AC cycle |
| Mounting on DIN Rail | TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715 TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715 |
| Overvoltage Category | III |
| Rated Current (I n ) | 16 A |
| Energy Limiting Class | 3 |
| Built-In Depth ( t 2 ) | 69 mm |
| Ambient Air Temperature | Operation -25 … +55 °C Storage -40 … +70 °C |
| Dielectric Test Voltage | 50 / 60 Hz, 1 min: 2 kV |
| Power Supply Connection | Arbitrary |
| Tripping Characteristic | C |
| Environmental Conditions | 28 cycles with 55 °C / 90-96 % and 25 °C / 95-100 % |
| Recommended Screw Driver | Pozidriv 2 |
| Number of Protected Poles | 3 |
| Rated Operational Voltage | acc. to IEC 60898-1 400 V AC acc. to IEC 60947-2 440 V AC |
| Contact Position Indication | Red ON / Green OFF |
| Mechanical Endurance (N endu ) | 20000 cycle |
| Rated Insulation Voltage (U i ) | acc. to IEC/EN 60664-1 440 V |
| Reference Ambient Air Temperature | 30 °C |
| Rated Short-Circuit Capacity (I cn ) | (400 V AC) 10 kA |
| Rated Impulse Withstand Voltage (U imp ) | 4 kV (6.2 kV @ sea level) (5.0 kV @ 2000 m) |
Les tarifs sont réservés à nos clients. Connectez-vous ou demandez un devis pour obtenir un prix et passer commande.